TECHNICAL SPECIFICATIONS

 1
Accuracy
For Power Class 1.0 IEC 1036/ IS13779
For Voltage 0.5% of reading (+/- 2 digits)
For current 0.5% of reading (+/- 2 digits)
 2
Voltage input Vn
3ph 4W (LT) 415 V ac (L-L) (-40% to +20%)
3ph 4W (HT) 110 V ac (L-L) (-40% to +20%)
3ph 3W (HT) 110 V ac (L-L) (-40% to +20%)
 3
Current Input In 
5A or 1A
 4
Starting Current
0.2% In (Class 1.0)
 5
Frequency
50Hz ± 10%
 6
Load Characteristics
Potential circuit < 8 VA
Current circuit < 0.5 VA
 7
Short time over current 
40 times In for 500 ms
 8
Case Material
Polycarbonate
Protected to IP51
 9
Display
Backlit LCD,
10mm height digits 
 10
Dimension (mm) 
96 W x 96 H x 105 D
 11
Weight
< 600 grams

CATALOG NOs.

 WI300FC5300
3 ph., 4 wire, 415 V, LT meter with 5 A CT
 WI300FC1300
3 ph., 4 wire, 415 V, LT meter with 1 A CT
 WI300FC53RS
3 ph., 4 wire, 415V, LT meter with 5 A CT + RS485 port 
 WI300FC13RS
3 ph., 4 wire, 415 V, LT meter with 1 A CT + RS 485 port
 WI300FC53DB
3 ph., 4 wire, 415 V, LT meter with 5 A CT (Bulk Pack)
 WI301FC13DB
3 ph., 4 wire, 415 V, LT meter with 5 A CT (Bulk Pack)
 WI301FC5300
3 ph., 3 wire, 110 V, HT meter with 5 A CT
 WI301FC1300
3 ph., 3 wire, 110 V, HT meter with 1 A CT
 WI301FC53RS
3 ph., 3 wire, 110 V, HT meter with 5 A CT + RS 485 port
 WI301FC13RS
3 ph., 3 wire, 110 V, HT meter with 1 A CT + Rs 485 port

ORDERING INFORMATION

a) Type of connection, 3 phase 3 wire or 3 ph 4 wire
b) PT input: 415 V / 110 V
c) CT input: 1A / 5 A
d) with / without RS 485 communication

Advertisements

INTELLIGENT PANEL METER QUASAR

Quasar is a multi display comprehensive measuring device for electrical parameters. It can be used as a parameter display device in all Control & Relay panels, PCCs, MCCs, Distribution boards, test benches, test equipments, machine tools, power management systems and reactive power compensation systems. The unit utilizes a Micro controller based design with a state of the art, backlit, custom made LCD display.

Quasar can be used in both HT and LT applications. In case of LT, the meter can be connected to 415 V line-to-line voltages directly. In case of HT, the meter receives inputs from external CTs and PTs. The CT/PT ratios can be programmed in the meter so that the measurements are direct reading, without the need for scaling.

Micro controller based design
Display of:
Instantaneous / Cumulative /
Calculated values
DIN standard 96 x 96 mm enclosure
21 screens with 3parameters per screen
Class1 accuracy
3ph. 3wire / 3ph. 4 wire
Max. / Min. values
RS485 communication
Display of total harmonic distortion

FRONT PANEL CONTROLS

Up/Dn push buttons for scrolling
Mode selector push button for feeder parameters programming
Reset push button for resetting the integrated values